A boardroom grows from 12 to 18 seats. Calculate the winter heating duty, apply heat recovery and decide which part of the system carries the load.

Published by MEPFlow · Methods and limitations · Primary references

November 21, 2026 5 min read Updated November 21, 2026

Use the method while you read

Follow the worked examples, check your inputs and use the related MEPFlow tool to explore your own design.

Calculate room fresh air in L/s and m³/h
In this guide: jump to a step

A larger meeting room can require a larger outdoor-air heating coil even when its walls and windows do not change. Follow the extra six occupants through the winter design calculation before updating the fan coil or air handling unit schedule.

The example uses a Guide A boardroom people rate and a sensible air heat balance. The air properties, temperatures and recovery effectiveness below are illustrative design inputs. They can be replaced with the values for a real project.

For a room-by-room design, use MEPFlow’s heating and cooling load calculation software to connect traced floor-plan geometry with envelope, weather and peak-load results.

Calculate the incoming fresh air duty

The revised boardroom seats 18 people. At 10 L/s per person its outdoor airflow is 180 L/s, or 0.180 m³/s. For this example, take outdoor air at −5 °C, the indoor design temperature at 20 °C, air density at 1.20 kg/m³ and specific heat at 1.005 kJ/(kg·K).

The temperature rise is 25 K. Heating the outdoor air to room temperature requires 1.20 × 1.005 × 0.180 × 25 = 5.427 kW. The original 12-seat room required 3.618 kW at the same conditions. The change in fresh-air heating duty is 1.809 kW.

Sensible duty (kW) = ρ × cp × outdoor airflow (m³/s) × temperature rise (K)

Use cp in kJ/(kg·K). Convert L/s to m³/s by dividing by 1,000 before multiplying.

Apply sensible heat recovery to the temperature rise

Assume balanced supply and extract, return air at 20 °C and 60% sensible temperature effectiveness at the design operating point. The air leaving the recovery device is −5 + 0.60 × 25 = 10 °C. The downstream coil now raises 0.180 m³/s from 10 °C to 20 °C, requiring 2.171 kW.

The outdoor-air volume stays at 180 L/s in both revised designs. For equipment selection, obtain the manufacturer’s performance at winter conditions and account for bypass, defrost and the operating sequence.

Sensible winter outdoor-air duty, rounded to two decimals
Design caseFresh airTemperature rise across heaterHeating duty
Original 12 seats, no recovery120 L/s25 K3.62 kW
Revised 18 seats, no recovery180 L/s25 K5.43 kW
Revised 18 seats, 60% sensible recovery180 L/s10 K2.17 kW

Take the next step on your own floor plan

Create a MEPFlow account to work through loads, ductwork, domestic water or hydronic layouts in your browser.

Start free trial

Assign the duty to the equipment that supplies the heat

If the air handler delivers fresh air at room temperature, the central heater carries the residual outdoor-air duty. Adding the same 2.17 kW to the room terminal would count it twice. If the central system supplies cooler air, split the temperature rise at the actual supply condition.

For example, with 10 °C leaving recovery, a central coil delivering at 16 °C handles 1.30 kW. Raising that air the remaining 4 K in the room takes 0.87 kW. Together they still total 2.17 kW. Fabric transmission, infiltration and other room duties are separate line items.

Hand over both the airflow and its treatment

A useful issue sheet names the room, ventilation basis, occupancy, outdoor airflow, outdoor and supply temperatures, recovery assumption and equipment serving the duty. An airflow value alone cannot tell the next designer whether the central plant or zone terminal is responsible for the heating.

MEPFlow carries the selected room ventilation rate into the heating and cooling load workflow. Review the thermal treatment in Heating & Cooling Loads, or change the headcount in the CIBSE fresh air calculator. For summertime latent duty, use the humidity or enthalpy conditions as well as the dry-bulb temperatures.

Frequently asked questions

Does 60% heat recovery reduce the required fresh air by 60%?

The recovery device changes entering air temperature. Keep the design outdoor airflow and calculate the heating duty using the temperature rise that remains.

Does the worked figure represent the whole room heat loss?

It represents sensible heating of the specified outdoor air. The room heat balance also needs its envelope, infiltration and other applicable terms.