Skip to content
HVAC Loads

CIBSE Guide A fresh air rates for offices and meeting rooms

An office fit-out adds six meeting-room seats. Work through the revised fresh air schedule and see which figures belong in the design handover.

Published by MEPFlow · Methods and limitations · Primary references

November 21, 2026 5 min read Updated November 21, 2026

Use the method while you read

Follow the worked examples, check your inputs and use the related MEPFlow tool to explore your own design.

Calculate room fresh air in L/s and m³/h
In this guide: jump to a step

A tenant can add seats without moving a single partition. For a boardroom designed on a per-person basis, the fresh air calculation changes as soon as the seating brief does. The floor area alone will miss it.

This worked example uses the office entries in Guide A (2015), Table 1.5, with non-smoking occupancy. The figures below are outdoor-air duties at the stated headcounts. The example assumes both rooms are fully occupied at the same time.

For a room-by-room design, use MEPFlow’s heating and cooling load calculation software to connect traced floor-plan geometry with envelope, weather and peak-load results.

Read the room description and the units together

The office entries used here give 10 L/s per person. Use the occupancy in the design brief, such as the seats shown on an agreed layout. Where people routinely stand or hot-desk, confirm the intended peak occupancy with the client before fixing the rate.

Look at the units beside the source entry. Some rows elsewhere in the table describe extract flow or air changes per hour. Those require their own inputs and calculation. A blank people-rate cell cannot justify a zero outdoor-air duty.

Room outdoor air (L/s) = design occupants × outdoor air rate (L/s per person)

Multiply L/s by 3.6 to express the same physical airflow in m³/h.

Build the room schedule for the fit-out

The open-plan office has 24 workstations. The boardroom originally had 12 seats and now has 18. Only the occupancy of the boardroom changes. The original two-room sum was 360 L/s. The revised sum is 420 L/s under the same simultaneous-use assumption.

Illustrative design schedule using Guide A office entries on p. 1-12
Room and revisionPeopleRateFresh air (L/s)Fresh air (m³/h)
Open-plan office2410 L/s per person240 L/s864 m³/h
Boardroom, original1210 L/s per person120 L/s432 m³/h
Boardroom, revised1810 L/s per person180 L/s648 m³/h

One room, one revision

The original and revised boardroom rows are alternatives. Include only the current row in the floor total.

Take the next step on your own floor plan

Create a MEPFlow account to work through loads, ductwork, domestic water or hydronic layouts in your browser.

Start free trial

Know when a different check governs

An office meeting room, a dwelling bathroom and a production area can all appear in one project file. Their ventilation duties can have different purposes. For a volume-based brief, establish the room volume and design air changes. For a fixed extract duty, establish the airflow path and replacement air. For process emissions, identify the source and capture requirement.

Keep the occupant schedule separate from any allowance for different occupancy times. To claim diversity at a common air handler, record the operating scenario and confirm it is permitted by the design brief. A room sum on its own gives no evidence for a diversity factor.

Record the change in MEPFlow

In Heat Loads, select CIBSE A 2015 in Design basis, choose the room type in the Ventilation editor and enter the design occupants. The app supports 62 Table 1.5 entries with numerical people rates. Other entries identify why the room needs separate assessment.

A project-level selection changes the choices available to the designer. Apply the room type to each relevant room or a selected group, then recalculate. Review the room’s airflow, ventilation load and source in the export. If an engineer substitutes a project-specific rate, the room records a manual input.

Try the same occupancy change in the free CIBSE ventilation calculator, or follow the fresh-air heat loss example to see the effect on duty.

Frequently asked questions

Can I use a room’s total supply air as its fresh air rate?

Use the outdoor component for this check. A recirculating supply can carry additional airflow to meet heating or cooling demand. Record both quantities if they differ.

Which edition does MEPFlow use?

MEPFlow uses the supported people-rate entries from Guide A 2015, Table 1.5. The January 2021 corrigenda apply to that edition. They did not change these table rates.

Continue the engineering workflow

Put this guide into practice with MEPFlow

Move from the calculation method into a connected browser-based design workflow while keeping the assumptions visible for engineering review.

Start free trial

Primary references

Sources and further reading for the methods discussed in this guide.