CIBSE Guide B2 ventilation rates and the IDA categories

Two designers can enter the same headcount and get different results. A 24-person room shows exactly what changes when the specified indoor air quality category changes.

Published by MEPFlow · Methods and limitations · Primary references

November 21, 2026 5 min read Updated November 21, 2026

Use the method while you read

Follow the worked examples, check your inputs and use the related MEPFlow tool to explore your own design.

Calculate room fresh air in L/s and m³/h
In this guide: jump to a step

An air schedule arrives with 300 L/s of fresh air for 24 people. Another schedule shows 192 L/s for the same room. Before looking for a unit conversion error, check the specified indoor air quality category. Both figures can follow from the same multiplication.

Guide B2 (2016), Table 2.4 gives default people rates by IDA category, taken from BS EN 13779:2007. They apply to the low-pollution, clean-outdoor-air case discussed in the guide. Record which published edition the project brief calls for, especially on a European project that specifies a different EN edition or category system.

For a room-by-room design, use MEPFlow’s heating and cooling load calculation software to connect traced floor-plan geometry with envelope, weather and peak-load results.

Translate the specified category into room airflow

For this 24-person worked example, IDA 2 gives 24 × 12.5 = 300 L/s. IDA 3 gives 24 × 8 = 192 L/s. That 108 L/s difference is a change in the design assumption. Seek agreement on the required indoor air quality before using either duty for equipment selection.

Calculated outcomes for one 24-person room using the Guide B2 Table 2.4 defaults
Specified categoryDefault L/s per personRoom fresh airEquivalent m³/h
IDA 1 · High20480 L/s1,728
IDA 2 · Medium12.5300 L/s1,080
IDA 3 · Moderate8192 L/s691.2
IDA 4 · Low5120 L/s432

Set out why that category applies

An IDA label describes the indoor air quality basis used for this calculation. It is a separate decision from identifying a room as an office or lecture hall. Guide B2 also discusses an office rate in §2.2.3.2. For a brief using that 10 L/s per person option, the same 24 people would give 240 L/s.

If the specification says only “ventilate to CIBSE”, clarify whether it calls for a Guide A room rate, the B2 office guidance or a particular B2 IDA category. Put the approved choice and the design headcount on the room schedule. A higher or lower numerical result alone cannot settle which method applies.

Take the next step on your own floor plan

Create a MEPFlow account to work through loads, ductwork, domestic water or hydronic layouts in your browser.

Start free trial

Keep extract and heat recovery on their own lines

A per-person outdoor-air rate covers only the stated occupancy-based duty. Review extract, contaminants and replacement air separately, including any more demanding project requirement. Use the design brief and the relevant rules for the building location when reconciling those flows.

Heat recovery affects the temperature of the incoming air and therefore the heating duty. It does not remove the need to deliver the specified outdoor-air volume. Keep the fresh-air set point and the assumed recovery performance as separate schedule entries.

Apply B2 alongside the other design bases

In MEPFlow Heat Loads, select CIBSE B2 2016, then apply the category to the room or a group of rooms. The app multiplies each room’s own design occupancy by its selected rate. The B2 people-rate calculation has no floor-area term or ASHRAE zone-effectiveness multiplier.

The project may also contain rooms using Guide A or ASHRAE 62.1. The room report retains each selection. For a review, record the edition, category, occupancy, airflow and any manual override. Use the free calculator to reproduce the numbers above, or see how the software handles all three methods.

Frequently asked questions

Is IDA 2 the same as a room type in Guide A?

IDA 2 is an indoor air quality category. Guide A Table 1.5 is organised by use of space. Select the approach specified for the room.

Is a B2 category a regulatory minimum for every UK office?

The B2 defaults are design guidance with stated assumptions. The applicable national requirements and project specification determine what the design must demonstrate.

Continue the engineering workflow

Put this guide into practice with MEPFlow

Move from the calculation method into a connected browser-based design workflow while keeping the assumptions visible for engineering review.

Start free trial

Primary references

Sources and further reading for the methods discussed in this guide.