Duct Size Calculator for Round and Rectangular Ducts
Free online calculator · No signup required
Enter airflow and a friction rate or velocity to size round and rectangular ductwork. Use CFM or L/s, compare sizes, and check an existing duct.
Air properties and calculation basis
- Density
- 0.075 lb/ft³
- Dynamic viscosity
- 0.0432 lb/(ft·h)
- Specific heat
- 0.24 Btu/(lb·°F)
- Energy factor
- 1.08 Btu/(h·°F·CFM)
Results
Enter both known values to size the duct.
See MEPFlow in action
Size the whole duct network automatically.
Connect supply and return terminals on your floor plan. MEPFlow keeps airflow, duct sizes, velocity and pressure results together as the layout changes.
7-day free trial. No card required. Calculator inputs do not transfer automatically.
How to use the duct size calculator
- Choose Imperial for CFM and inches, or Metric for L/s and millimetres.
- Choose Size by friction for equal-friction sizing, Size by round velocity for a velocity check, or Check a round duct for an existing size.
- Enter the two known values. For a rectangular duct, set the fixed side and review the solved side and actual velocity.
- Choose an available manufactured size and check the revised velocity and friction. Include fittings and equipment when calculating the system pressure requirement.
Example: duct size for 1,000 CFM
Suppose the airflow is 1,000 CFM and the selected round-duct velocity is 1,000 ft/min. The required area is 1 square foot. A circular duct with that area has an inside diameter of 13.54 inches.
Selecting a 14-inch round duct gives about 935 ft/min. A 12 × 12-inch rectangular duct has the same one-square-foot area and a velocity of 1,000 ft/min, but it does not have the same friction loss as the equal-area round duct. Use the rectangular equal-friction result when pressure loss is your sizing basis.
Check the example in the calculatorDuct sizing formulas
Area (ft²) = airflow (CFM) ÷ velocity (ft/min)
Round diameter (in) = 12 × √[4 × CFM ÷ (π × velocity)]
Area (m²) = airflow (L/s) ÷ [1,000 × velocity (m/s)]
Rectangular area = width × height
For round and rectangular ducts, air velocity equals volumetric airflow divided by the actual cross-sectional area. Equal-friction sizing additionally accounts for air properties, duct roughness and the shape of the section.
Round vs rectangular duct sizing
Round ducts use less perimeter for a given area. Rectangular ducts can fit shallower spaces, but their aspect ratio affects the required area and friction. The equivalent round diameter is a pressure-loss comparison; it is not the rectangular duct's hydraulic diameter or an equal-area diameter.
If a rectangular result fits the ceiling but its air velocity is too high for the acoustic requirements, increase the section and check again. A calculator cannot choose the room noise criterion or the available installation space for you.
Calculation method and air properties
The solver uses continuity, Reynolds number, the Colebrook–White Darcy friction factor and Darcy–Weisbach pressure loss. Its reference roughness is 0.0007 ft (0.21336 mm), matching the existing MEPFlow duct-sizer basis. Adjust air density and viscosity in the calculator when required.
Equivalent round diameter = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25
This Huebscher relationship uses a and b in the same units. The actual rectangular velocity is reported separately. Results describe a straight section; joints, bends, transitions, leakage and system effects require additional review.
Frequently asked questions
What size duct do I need for 1,000 CFM?
It depends on the design velocity or friction rate. At 1,000 ft/min, the equal-area round diameter is 13.54 inches. A 14-inch round duct carries 1,000 CFM at about 935 ft/min. Check its friction rate, available fan pressure and noise criteria before selecting it.
Can I calculate rectangular duct size from CFM?
Yes. Enter airflow and a friction rate, then fix one rectangular side to suit the ceiling or shaft. The calculator finds the other side on an equal-friction basis and reports the rectangular duct's actual velocity separately.
What friction rate should I use?
Choose it from the available pressure budget and the effective duct length. The starting value shown is an example, not a design requirement. Longer systems, sensitive rooms and limited fan pressure can require different values.
Is this an online ductulator?
Yes. It solves airflow, velocity, friction rate and equivalent round diameter from any two known values. The three shortcuts cover common checks; the individual Known boxes also allow other pairs.
Can I use it for flexible duct?
The default roughness and round/rectangular relationships are intended for the stated rigid-duct calculation basis. Flexible duct performance depends strongly on stretch, compression and bends. Use the manufacturer's pressure-loss data for the installed condition.
Does it calculate fan external static pressure?
It reports straight-duct friction. Fan selection also needs fitting losses, filters, coils, terminals and other components along the controlling path. Add those losses using the fan manufacturer's pressure convention.